Technical Approval No. for S 90 - S 120:
Z-19.15-1762 Wall Penetration Seal
Z-19.15-1763 Floor / Ceiling Penetration Seal
Elastic firestop bricks for wall and floor/ceiling penetrations, designed for the protection of single and bunched electrical lines and cables of all types (including optical fibre cables) – without restrictions imposed on each cable’s overall conductor cross-section – as well as of their supporting structures (cable troughs, trays and ladders) made of steel, aluminium or plastics. Also permitted for the protection of penetrating single steel and plastic pipes < 15 mm.
Walls S 90 – S 120: Installation in masonry or concrete walls of at least 10 cm thickness as well as in lightweight partitions of at least 10 cm thickness. Floors/ceilings S 90: Installation in concrete floors/ceilings of at least 15 cm thickness. Required seal thickness for S 90 – S 120: 23 cm.
Max. permissible seal thickness:
In the first step, clean and dust the penetration opening. Then cut FLAMRO BSB to size crosswise and install the elements with staggered joints (13 cm) in such a way that the seal fits flush with the building component. Any remaining gaps must be sealed with FLAMRO BSS.
Distance requirements for walls: distance between individual cable layers as well as distance between the uppermost cable layer and the top inside surface of the through-penetration opening at least 40 mm; distance from the lateral inside surfaces and from the bottom inside surface of the opening 0 mm. Distance requirements for floors/ceilings: Rim zone at least 0 mm, distance between cable layers at least 40 mm.
The cable penetration seal must be permanently labelled by the installation company. The identification label, which is available from FLAMRO Brandschutz-Systeme GmbH, has to be affixed to the building component next to the seal.
(Chapter 5 of the Technical Approval document)
FLAMRO BSB/BSS remains resilient after curing, which makes retrofitting very easy and convenient. An annular space of at least 1 cm must be provided and then sealed with FLAMRO BSB / BSS.